VX-3008F

WhatsApp For Pricing

The VX-3008F frame is one of three system managers of TOA’s VX-3000 series rack-mount type public address
and voice evacuation system certified according to the European Standard EN 54-16. It provides 8 speaker line
outputs/zones that can be switched between two amplifiers. This allows broadcasting two different audio signals
simultaneously on the speaker lines. Up to three additional VX-3008F frames without amplifiers can be added to
expand the number of zones. The amplifier modules can be easily mounted and removed. Up to 3 power amplifier modules of different wattages can be mounted, two of which amplifiers drive the speaker lines, while one is a
standby amplifier. The standby amplifier, when mounted, can be shared among other VX-3000F units. Each amplifier channel has the following DSP functions: different filter types (PEQ, HPF, LPF, shelving, CD-horn EQ, notch),
compressor and delay that enables appropriate acoustic adjustment for any broadcast area. The smart ANC function enables the control of ambient noise and is not affected by the audio signal it controls. Therefore, the sensor’s installation location is not critical. The monitoring of the speaker lines can be selected between impedance
monitoring with selectable pilot tone or by end-of-line modules.The VX-3008F has 4 balanced audio input terminals from microphone up to line level sensitivity, with phantom power selection for microphone use. The inputs
can also be set for receiving an emergency broadcast from another VA system of higher priority and broadcast it
under the condition of the emergency mode. Up to 8 remote microphones can be connected via RJ45 ports; two
of which can be emergency microphones. The following DSP functions are available for each input channel: different filter types (PEQ, HPF, LPF, shelving) and compressor. Helpful features such as feedback suppressor or voicecontrolled broadcast activation (VOX) enhance the usability of the system.

Share it:
Features
Related Products

Features

Indicator

power, run, CPU off, LAN status, RM status, emergency status faults: general, network, EMG microphone, fuse, power, CPU, zones, amplifier status: signal, peak, operate, power

Power source.

31 V DC operating range: 20 – 40 V DC)

Audio input

4 balanced channels, nominal sensitivity between -60 dBV and -20 dBV, can be attenuated by potentiometer behind front panel,

phantom power selectable

Frequency response.

40 Hz – 20 kHz (±1 dB)

Power source.

31 V DC operating range: 20 – 40 V DC)

Distortion.

< 1 % (at 1 kHz)

Power / current consumption

max. 85 W at 31 VDC

Control input

16 (by contact) + 2 (by 24 VDC polarty change)

Frequency response.

40 Hz – 20 kHz (±1 dB)

Power / current consumption

max. 85 W at 31 VDC

Control output

Open collector: 8 + 3 (CPU OFF), Relay (125 VDC, 5 A): 8

S/N ratio.

60 dB(A) (or more)

Control input

16 (by contact) + 2 (by 24 VDC polarty change)

Control output

Open collector: 8 + 3 (CPU OFF), Relay (125 VDC, 5 A): 8

Input / Output

Speaker Output: 8 zones

Audio Input: 4 (Line: -20 dBV / Mic: -60 dBV, phantom power selectable)

Connection

RJ45: control inputs x 2, control outputs (open collector) x 2, DS link x 1, remote microphones x 2, LAN x 2, analog link x 2, Removable screw terminals: control outputs (relay), zone outputs, standby amplifier bus, extension links, power input, audio inputs.

Finish.

Steel plate, surface-treated, 30 % gloss, paint, black,

Operating humidity.

90% or less

Operating temperature.

-5°C to +45°